Fire Safety Learning Center

Articles and other information related to fire safety equipment and procedures in Illinois.

Servicing requirements for fire extinguishers in Chicago

These rules apply to ABC dry chemical extinguishers only. NFPA 10 defines the maintenance procedures required for portable fire extinguishers. All multi-purpose ABC extinguishers must have maintenance performed on an annual basis. After performing these steps, the technician will apply a new colored tag (Including his or her license information) to the extinguisher to clearly specify that maintenance has been performed. Every six years the fire extinguisher must be completely torn down (taken apart), recharged and rebuilt. During this process, key parts within the extinguisher are replaced. A special maintenance sticker is added to the extinguisher cylinder to record the date...

Continue reading
  2902 Hits

Fire Extinguisher requirements for condo buildings in Chicago

Unless your Association is both under three stories in height and has a total floor area of less than 3,000 square feet, your building must have portable fire extinguishers. (Very few condo buildings will have a total area of less than 3,000 square feet) For most condo buildings, determining the number and type of fire extinguishers required to protect the common areas is fairly simple. Typically, you will need one, multi-purpose (ABC) dry chemical fire extinguisher on each floor of the building. The extinguisher would normally be installed in the hallway where it can be easily accessed by residents. NFPA 10...

Continue reading
  7242 Hits